Type CAB-CC compact |
|
|
• |
Type CAB-CC
- compact - |
|
|
|
|
|
rated voltage [kV] |
up to 36 |
|
rated busbar current [A] |
up to 630 |
|
rated short-time current 1s [kA] |
up to 20 |
|
|
The CAB-CC compact system is an SF6 insulated metal enclosed switchgear
for indoor installations in universal applications from ringed distribution
networks to complex distribution switchgear according to the needs
of our clients. The SF6 tank is made out of stainless steel and is
fully welded. The panel modules are extendable on both sides by means
of standardized connectors. The CAB-CC is of course also extendable
using our modular system CAB CM.
The CAB-CC is available with following function schemes:
CC0L1P |
- Cable termination, one transformer
feeder for use with wind
generators |
CC0L1L1P |
- Cable termination, one line function, one transformer
feeder for use with wind generators |
CC0L2L1P |
- Cable termination, two line function, one transformer
feeder for use with wind generators |
CC0L0L1P |
- Two cable termination, one line function, for
use with wind
generators |
CC0L1L1PSS |
- Cable termination, one line function, one transformer
feeder, one cable riser for use with wind generators |
CC3L-n |
- Three line functions, extendable on one (n=1)
or two (n=2) sides |
CC1L1P-n |
- One line functions, one transformer feeder, extendable
on one (n=1) or two (n=2) sides |
CC2L1P-n |
- Two line functions, one transformer feeder, extendable
on one (n=1) or two (n=2) sides |
CC2L1PSP |
- Two line functions, one transformer feeder, one
bus sectionalizing function |
CC2L1PSB |
- Two line functions, one transformer feeder, reduced
height for use in compact transformer substations |
CC2L2P-0 |
- Two line functions, two transformer feeder, not
extendable |
CC3L1P-0 |
- Three line functions, one transformer feeder,
not extendable |
Other functions are available on request.
All panels are type tested according to IEC 60298. The
main components used comply to IEC 60265-1, IEC 62271
(100, 102, 105), IEC 60137, DIN 4763,
IEC 60282-1. The
panels are designed for use under normal operating conditions.
|
Advantages |
• |
Insensitive
to environmental conditions |
• |
Suitable
for use in floodable underground substations |
• |
High
electrical and mechanical endurance |
• |
Special
functions available for use with wind generators |
• |
Compact
design |
• |
Minimum
amount of maintenance |
• |
Wide range of accessories |
|
Some
Technical Features |
• |
Degree of protection panel IP2X |
• |
Degree
of protection SF6 tank IP67 |
• |
Arc
proof tested 20kA /1s |
• |
Ambient
temperature from -10°C
up to +55°C |
• |
Completely
welded stainless steel tank |
• |
Extendable
with compact panel type CAB-CC |
• |
Manual
and motor operation (option) |
• |
Auxiliary contacts up to 4NO
+ 4NC |
• |
Remote control (option) |
|
|
|
|
|
|
|
|
|